The Cleveland Controls NS2 Series is a compact, economical family of air pressure sensing switches for residential and light commercial HVAC applications. The most common application is induced draft fan proving and combustion air proving on gas furnaces and boilers — the switch verifies the draft inducer is running before ignition is allowed to proceed. Two variants:
NS2 with fixed set-point (e.g. NS2-1018-00, NS2-0461-00, NS2-1166-00): Factory-calibrated at a specific set point. Part numbers ending in a non-zero suffix (NS2-XXXX-00, -01, etc.) are typically OEM-specified fixed set-point models. The set point is not readable directly from the part number digits — always match the complete part number or verify against the Cleveland Controls datasheet or your equipment's service manual.
NS2-0000-xx field-adjustable kits (e.g. NS2-0000-00, NS2-0000-01, NS2-0000-03): Field-adjustable range of 0.10"–10.0" W.C. Includes springs, orifice restrictors, and brackets. Used when an exact OEM fixed switch is unavailable or when a field-configurable replacement is needed.
Construction (both variants): Glass-filled polycarbonate housing, post-cured silicone diaphragm, integral SPDT snap-acting switch, three 90° male quick-connect terminals. Color-coded ports: high pressure = black, low pressure = gray. Operating range: 0.05"–10.0" W.C. Max pressure: 14" W.C. Operating temperature: −40°F to 190°F (−40°C to 88°C). Product life: 100,000 cycles minimum. Approvals: UL, CUL, CSA, CE, Australian Gas Association.
Fixed Set-Point (OEM) or Adjustable Kit
0.05"–10.0" W.C. Range
SPDT · SPST Options
Glass-Filled Polycarbonate
−40°F to 190°F
100,000 Cycles Min.
UL · CUL · CSA · CE
Fan Proving · Combustion Air