Honeywell T775 Series 2000 Selection Guide: The Right Model, Spec'd in 5 Steps
Jun 24th 2026
The T775 replaced 38 older Series 1000 models — including the now-obsolete T991A. This guide walks you through every model, every key spec, and the full T991A cross-reference so you can find your replacement fast.
The T775 Series 2000 is Honeywell's current-generation electronic stand-alone temperature controller for commercial HVAC, boiler, chiller, agricultural, and process applications. It senses temperature remotely via a wired PTC sensor and provides switched relay outputs, modulating analog outputs (0–10 Vdc, 2–10 Vdc, 4–20 mA, Series 90), or floating outputs to control dampers, valves, pumps, compressors, and other loads.
Fourteen T775 models replace 38 older Series 1000 controllers — including every T991A variant. If you're looking at a T991A right now, it's discontinued. The T775 is what you need.
Important — operating control only: The T775 is an operating control, not a limit or safety control. If your application requires a safety or limit function, a separate listed safety device is required in addition to the T775.
All T775 controllers are field-mountable in any orientation on a panel or wall. Power options are 24, 120, or 240 Vac (50/60 Hz). Every model includes a digital input for setback or disable, a built-in time clock scheduler with two settable periods per day, keypad lockout, sensor calibration, and configurable minimum off time.
The T775 family branches into standard models (A, B, M, R) and special-application models (L, P, U, S). Answer these five questions and the right model falls out.
Relay-only models (T775A, T775B) switch loads on and off based on a setpoint. Modulating models (T775M, T775R with mod outputs) provide 0–10 Vdc, 2–10 Vdc, 4–20 mA, Series 90, or floating outputs for proportional control of valves, dampers, and actuators. Most boiler and chiller valve applications need modulating output.
T775 relay models range from 1 to 4 SPDT relays per base unit. The T775L and T775P can expand to 8 or 12 stages total using T775S expansion modules. Count your loads: each compressor stage, pump, boiler stage, or fan requires one relay output.
Reset models (T775R, T775P, T775L, T775U) automatically adjust the control setpoint based on outdoor temperature — as it gets colder outside, the hot water supply setpoint rises. This is standard on boiler reset applications. If you need reset, you must use a reset-capable model and a second sensor for outdoor air temperature.
Three special models cover unique use cases: T775P for multi-stage boiler control with pump output and reset; T775L for staged sequencing of chillers and multi-compressor systems; T775U for non-temperature inputs like pressure or humidity via 0–10 Vdc or 4–20 mA sensors. If none of these apply, stay with the standard A/B/M/R models.
Most T775 models are NEMA 1 (indoor, dry). Four models (T775B2016, T775B2024, T775M2014, T775M2022) are available in NEMA 4X enclosures rated for washdown, animal confinement, pool equipment rooms, and other wet or corrosive environments. NEMA 4X models ship with the T775-SENS-WR water-resistant sensor instead of the standard sensor.
Tell us your application, number of stages, whether you need reset, and your voltage — we'll get you to the right T775 part number fast.
Once you've answered the five questions, here's what each model delivers.
The T775A2009 is the simplest T775 — one SPDT relay output, one sensor input, standard NEMA 1 enclosure. It handles basic on/off temperature control for single loads like fans, pumps, or heating/cooling equipment where one setpoint controls one output. If your old T775A1001 needs replacing, this is the direct successor.
Choose the T775A when: You need simple on/off control with a single relay and single sensor, your application doesn't require modulating output or multiple stages, and NEMA 1 indoor mounting is acceptable.
The T775B series expands the relay count to 2 or 4 SPDT outputs and adds a second sensor input. This covers multi-stage cooling towers, dual-compressor systems, two-stage heating/cooling, or any application requiring multiple switched outputs from a single controller. Four T775B models give you NEMA 1 or NEMA 4X in 2-relay or 4-relay configurations.
The T775B also supports a floating output option (eliminates two SPDT relays, used to drive floating actuators directly). Sensor B can serve as a high/low modulating limit reference on select configurations.
Choose the T775B when: You need 2–4 relay outputs for on/off staging, want NEMA 4X for wet or washdown environments, or are running a multi-stage cooling or heating system without modulating output.
The T775M series is the workhorse modulating controller and the most common T991A replacement. It provides up to two independent analog outputs configurable for 0–10 Vdc, 2–10 Vdc, 4–20 mA, or Series 90 — plus up to 4 SPDT relay outputs depending on configuration. The T775M2006 (2 analog outputs, no relays, NEMA 1) is the standard direct drop-in for most T991A applications.
PI and PID control is standard on all modulating outputs, with configurable integral and derivative times and anti-integral wind-up. The modulating high/low limit feature lets Sensor A control output while Sensor B acts as a high or low limit guard — useful for freeze protection or overheat cutback on a secondary loop.
NEMA 4X variants (T775M2014, T775M2022) are available for washdown or outdoor cabinet installations.
Choose the T775M when: Your application requires proportional control of a valve, damper, or actuator via an analog signal; you're replacing a T991A; or you need PI/PID control with up to two independent modulating outputs.
The T775R series adds outdoor reset to the standard T775 platform. Reset programming requires only four values: high and low control temperatures, and the corresponding high and low outdoor temperatures. As the outdoor temperature drops, the hot water setpoint automatically rises — saving energy by delivering only the supply temperature the building actually needs.
Five T775R models cover 2 or 4 relays, 0 or 2 analog outputs, and combinations thereof. All include two sensor inputs and reset as standard. The T775R is also used for chilled water reset — the inverse logic (as outdoor temp rises, chilled water setpoint drops) is simply the cooling mode configuration.
Choose the T775R when: Your application is hot water or chilled water reset, you're controlling a boiler or chiller with outdoor air compensation, or energy codes require supply water temperature reset.
The T775P2003 is purpose-built for multi-stage boiler systems. It provides 4 SPDT relay outputs (expandable to 8 or 12 with T775S modules), a dedicated pump output using the last relay, outdoor reset, and three sensor inputs (supply, return, and outdoor). Stage sequencing options include standard, first-on/first-off, or equal run time — protecting boilers from short-cycling and balancing wear across multiple units.
The T775P also includes a Digital Output alarm (low voltage) configurable for minimum, maximum, or differential temperature trips — the only base T775 model with this feature.
Choose the T775P when: You're controlling a multi-stage boiler system with a primary pump, need outdoor reset, want equal run time or first-on/first-off staging, or need built-in alarm output capability.
The T775L2007 sequences multiple relay stages across one or two independent setpoints — ideal for multi-compressor chiller systems, reciprocating chiller control, or any application where you need to stage multiple loads with independently configurable heat and cool setpoints. Stage distribution between the two setpoints is freely programmable (e.g., 3 heat / 4 cool, 5 heat / 1 cool).
Up to two T775S expansion modules can be added for a total of 12 staged relay outputs. Two additional relays are available for independent on/off control if not consumed by the staged loops. Outdoor reset is included standard.
Choose the T775L when: You're sequencing multiple chiller compressor stages, need two independent heat/cool setpoints on the same system, or require up to 12 stages with flexible distribution.
The T775U2006 accepts 0–10 Vdc or 4–20 mA sensor input for any process variable — pressure, humidity, CO₂, or any medium with an analog output. Compatible sensors include Honeywell H7625/H7635/H7655 humidity sensors, P7640A differential pressure transducers, and C7232/C7632 CO₂ sensors. Sensor B accepts a standard temperature input only (for reset applications).
Input range is configurable for pressure (up to ±500 PSI, ±30 in. w.c., ±3,000 Pa or kPa), humidity (0–100% RH), or temperature. This is the only T775 model that replaces the older H775 humidity and pressure controller line.
Choose the T775U when: Your controlled variable is pressure, humidity, or CO₂ rather than temperature, or you need a single controller to handle non-standard analog sensor inputs.
The T775S2008 is a 4-relay expansion module used only with the T775L or T775P base controllers. Up to two T775S modules can be added to bring total staged relay outputs to 8 (one T775S) or 12 (two T775S). The T775S has no standalone functionality — it only works wired to a T775L or T775P via the bus terminals.
Choose the T775S when: Your T775P boiler system exceeds 4 stages, or your T775L chiller sequencer needs more than 4 relay outputs.
Use this table to quickly confirm which model fits your application. NEMA 4X options are noted separately — all others are NEMA 1.
| Feature | T775A | T775B | T775M | T775R | T775P | T775L | T775U |
|---|---|---|---|---|---|---|---|
| Primary Use | Basic on/off | Multi-relay on/off | Modulating control | Reset + mod/relay | Multi-stage boiler | Chiller sequencing | Pressure / humidity |
| Relay Outputs | 1 | 2 or 4 | 0, 2, or 4 | 0, 2, or 4 | 4 (+pump) | 4 | 2 |
| Analog Outputs | None | None | Up to 2 | 0 or 2 | None | None | 2 |
| Outdoor Reset | ✗ | ✗ | ✗ | ✓ | ✓ | ✓ | ✓ |
| Expandable (T775S) | ✗ | ✗ | ✗ | ✗ | ✓ to 12 | ✓ to 12 | ✗ |
| Alarm Output (DO) | ✗ | ✗ | ✗ | ✗ | ✓ | ✗ | ✗ |
| Non-Temp Sensor | ✗ | ✗ | ✗ | ✗ | ✗ | ✗ | ✓ (4–20mA / 0–10V) |
| NEMA 4X Option | ✗ | ✓ | ✓ | ✗ | ✗ | ✗ | ✗ |
| T991A Replacement | — | — | ✓ Primary | Some models | — | — | — |
| Sensor Inputs | 1 | 2 | 2 | 2 | 3 | 2 | 2 |
The T991A is fully discontinued. Below are the confirmed Honeywell replacements. If your T991A model number isn't listed, call us — we'll look it up against the official cross-reference.
| Obsolete Model | Description | T775 Replacement |
|---|---|---|
| T991A1012 | Proportional temp controller, 55–175°F, 5 ft capillary, Series 90 | T775M2006 |
| T991A1061 | Proportional temp controller, 55–175°F, Series 90, 5 ft capillary | T775M2006 |
| T991A1079 | Proportional temp controller, 55–175°F, Series 90 | T775M2006 |
| T991A1194 | Proportional temp controller, 55–175°F, 5 ft capillary | T775M2006 |
| T991A1244 | Proportional temp controller, 55–175°F, 5 ft capillary | T775M2006 |
| T991A1350 | Proportional temp controller, 24' copper averaging element | T775M2006 |
| T991A1764 | Proportional temp controller, Series 90 output | T775M2006 |
Note on Series 90 output: T991A controllers with a 135-ohm Series 90 potentiometer output connect to Series 90 actuators. The T775M supports Series 90 output — you will need the included 340-ohm resistor connected across terminals R and W per the T775 wiring diagram. Verify the actuator is still Series 90 compatible before completing replacement.
Match your real-world scenario to the right T775 model. If your application spans multiple scenarios, call us.
Outdoor air sensor adjusts supply water setpoint as outside temperature drops. Standard on boiler systems for energy codes and efficiency.
→ T775R Series or T775P20034–12 staged boiler outputs with primary pump relay, equal run time sequencing, outdoor reset, and optional alarm output.
→ T775P2003 + T775S2008 (if >4 stages)Proportional control of a hot water valve, chilled water valve, or air damper via 0–10 Vdc, 2–10 Vdc, 4–20 mA, or Series 90 signal.
→ T775M SeriesMultiple reciprocating or scroll compressor stages with two independent setpoints, chilled water reset, and flexible stage-count distribution.
→ T775L2007 + T775S2008 (if >4 stages)On/off staging of multiple condenser fans or cooling tower fan stages from a single controller with setpoint and differential configuration.
→ T775B Series (2 or 4 relays)Installations in poultry houses, hog confinement, swimming pool mechanical rooms, or washdown areas requiring water-resistant enclosures.
→ T775B2016, T775B2024, T775M2014, or T775M2022 (NEMA 4X)Duct static pressure, differential pressure, or relative humidity control using a 0–10 Vdc or 4–20 mA analog sensor. Also compatible with Honeywell CO₂ sensors (output displayed in % rather than ppm).
→ T775U2006Have a T991A part number from the nameplate? We'll cross-reference it directly. Don't have the number — pipe size, media, voltage, and output type is enough to get you to the right T775.
→ Call (901) 458-2000Tell us your application — number of stages, whether you need reset, your sensor type, and your control signal — and we'll ID the right part number and ship it same day if it's in stock.
These specifications apply across the T775 Series 2000 family unless otherwise noted.
| Specification | Value |
|---|---|
| Power Supply | 24, 120, or 240 Vac; 50/60 Hz |
| Power Consumption | 8 VA max @ 60 Hz; 10 VA max @ 50 Hz |
| Operating Ambient | -40° to 140°F (-40° to 60°C) @ 60 Hz |
| Relay Rating (120 Vac) | 1/2 hp; 9.8 AFL, 58.8 ALR; 125 VA pilot duty |
| Relay Rating (240 Vac) | 1/2 hp; 4.9 AFL, 29.4 ALR; 125 VA pilot duty |
| Relay Rating (24 Vac) | 10A resistive |
| Analog Output Options | 0–10 Vdc (min 2,000Ω load), 2–10 Vdc, 4–20 mA (max 600Ω), Series 90, Floating |
| Sensor Type | 1,097Ω PTC @ 77°F (25°C) |
| Setpoint Range | -40° to 248°F (-40° to 120°C) |
| Sensor Accuracy | ±1°F @ 77°F ambient (standard sensor) |
| Sensor Calibration | ±10°F / ±10% of range for non-temp sensors |
| Time Clock | Two settable periods per day, all models |
| Volatile Memory | Date/time retained 24 hours after power loss; all other settings permanent |
| Dimensions | 8-5/32" H × 4-13/32" W × 2-15/16" D |
| Approvals | UL 60730-1, CuL, CE, C-tick |
Memphis Control Center is an authorized Honeywell distributor with T775 Series 2000 controllers in stock. Same-day shipping on in-stock orders by 2 PM CT. We'll cross-reference your T991A and get you the right T775 fast.
For emergencies, outside of business hours, call #901-604-7069