Thermocouple-powered, 100% shutoff, standing pilot safety valve. Operation: Press and hold the reset button to allow gas flow to the pilot only (internal flow design). Light the pilot burner. The thermocouple heats up and generates millivoltage that holds the safety valve electromagnet open. Release the reset button — if the pilot is burning correctly, the valve stays open. If the pilot goes out at any time, thermocouple output drops, the electromagnet releases, and the valve closes — shutting off 100% of gas to both pilot and main burner.
Applications: Commercial cooking equipment (fryers, ranges, griddles, ovens), boilers, unit heaters, kilns, dishwashers, industrial ovens, agricultural heaters.
Key specs: Natural gas and LP gas. Max 0.5 PSI (14" W.C.) inlet pressure. Cast aluminum body. Mounts in any position. Ambient temperature: standard models 30°–175°F, high-temp models 32°–300°F. Certifications: CSA; UL (H15CA and DA models); CE/UKCA (models without pilot adjust valve).
100% Gas Shutoff
No Electricity Required
Natural Gas · LP · LP-Air Mix
Max 0.5 PSI / 14" W.C.
CSA · UL (CA/DA) · CE/UKCA
Standard: 175°F · Hi-Temp: 300°F