Commercial HVAC & Boiler Service

Commercial Boiler Service | Mid-South | MCC
Commercial HVAC & Boiler Service

Commercial Boiler & HVAC Service
Across the Mid-South

Steam boiler down? Burner locking out? Low water cutoff failing inspection? Memphis Control Center has supported commercial and industrial boiler operations across the Mid-South since 1967. We know the equipment, we stock the parts, and we'll get you taken care of.

Mid-South since 1967 TN · AR · MS · AL · LA Parts in stock — same-day shipping Family owned
Service Coverage: Tennessee Arkansas Mississippi Alabama Louisiana Gulf Coast

55+ Years of Boiler & HVAC Controls Expertise

Commercial and industrial boiler systems don't fail on a convenient schedule. When a steam boiler goes down — whether it's a hospital, a food processing plant, a school, or a commercial building — the clock starts immediately. You need someone who knows the equipment and can move fast.

Memphis Control Center has been supplying commercial and industrial boiler controls, instrumentation, and parts to the Mid-South since 1967. That means we've seen virtually every failure mode on every major boiler system in service today. We know the difference between a nuisance low water cutoff shutdown and a genuine safety event. We know which burner controls are prone to flame amplifier failures. We know the gasket series that belongs on your 150 psi steam boiler.

When you contact us for commercial boiler or HVAC service support, you're not talking to a call center. You're talking to people who have been in this industry their entire careers — in Memphis, serving the Mid-South.

55+
Years in the Mid-South
Continuously serving commercial and industrial boiler operators since 1967 from Memphis, TN.
2 PM
Same-Day Parts Cutoff
Order common boiler controls and parts by 2 PM CT and they ship the same day. Don't wait on parts when your boiler is down.
5
States Covered
Tennessee, Arkansas, Mississippi, Alabama, and Louisiana — plus the Gulf Coast region.

Commercial Boiler & HVAC Service Scope

From emergency breakdowns to planned annual maintenance — here's a detailed breakdown of the commercial boiler and HVAC service we support across the Mid-South.

Steam Boiler Inspection & Repair

Full-service support for commercial steam boilers including fire-tube, water-tube, and cast iron sectional designs. Annual inspection prep and safety compliance support.

Annual boiler inspection & certification prep
Boiler tube cleaning & descaling
Handhole & manhole gasket replacement
Refractory inspection & repair
Pressure vessel repair & NDE testing support
Emergency boiler repair & startup

Burner Controls & Combustion Service

Burner control systems are one of the most common points of failure in commercial boiler operations. We support Honeywell 7800 Series and other major burner management systems.

Burner management system repair & replacement
Flame amplifier selection & replacement
Combustion air/fuel ratio tuning
Gas valve proving system (VPS) service
Pilot system repair & igniter replacement
Lockout fault code diagnosis

Low Water Cutoff Service & Replacement

The low water cutoff is your boiler's most critical safety control. Failure to trip during blowdown is a safety emergency. We support the full McDonnell & Miller lineup.

LWCO inspection, testing & blowdown procedure
Float-type & probe-type replacement
Series 67, 150S, 157S, PS-800 service
CSD-1 compliant installation & documentation
Nuisance shutdown troubleshooting
Proactive replacement at 10/15-year intervals

Boiler Gasket Replacement

Handhole and manhole gasket failures are one of the leading causes of unplanned boiler outages. Using the wrong gasket series for your pressure is a safety risk.

Topog-E® Series 180 (up to 180 psi steam)
Topog-E® Series 450 (up to 450 psi, asbestos-free)
Series 1000 spiral wound & Series 2000 graphite
Series 3000 expanded PTFE for worn flanges
Ajax legacy gaskets (discontinued boilers still in service)
Series selection by P/T conditions — we'll specify

Boiler Controls & Instrumentation

Modern commercial boilers run on sophisticated control systems. We support specification, supply, and service coordination of all major boiler control components.

Pressuretrol & aquastat replacement
Feedwater control & pump controller service
Steam pressure & temperature instrumentation
Modulating control valve service
Boiler sequencing & lead-lag controls
Control panel upgrade & retrofit

Hot Water Boiler & Hydronic Systems

Commercial hot water heating systems, chilled water systems, and hydronic distribution — pumps, controls, and all supporting equipment.

Hot water boiler service & repair
Bell & Gossett pump service & repair
Hydronic system balancing & commissioning
Expansion tank & air separator service
Zone control valve replacement
LWCO service on hot water systems
Boiler down right now? Call us — common parts ship same day by 2 PM CT from Memphis.

Boiler Types & Systems We Support

We support commercial and industrial boiler service across all major designs and fuel types. If your boiler isn't listed, call us — chances are we've seen it.

Commercial boiler types and service coverage
Boiler TypeFuelPressure RangeCommon ApplicationsControls We Support
Fire-Tube (Scotch Marine)Gas / Oil / Dual15–250 psiCommercial buildings, schools, hospitalsFull — burner, LWCO, gaskets, instruments
Water-TubeGas / Oil / Coal100–1,000+ psiIndustrial, power, large commercialFull — burner controls, drum level, safety
Cast Iron SectionalGas / Oil0–15 psi (steam)Residential, light commercial, schoolsFull — burner, LWCO (67/PS-800), gaskets
Condensing BoilerGas0–15 psiHigh-efficiency commercial heatingBurner controls, modulating valves
Electric BoilerElectric0–150 psiClean rooms, specialty applicationsLWCO, pressure controls, instrumentation
Thermal Fluid / Hot OilGas / OilLow pressure / processProcess heating, food, chemicalBurner controls, temperature instrumentation
Steam Generator (Once-Through)Gas15–150 psiCar washes, food processing, laundryFull — burner, LWCO, safety controls

Manufacturers We Support

Cleaver-Brooks
CB, CB-LE, CBLE, CBEX series firetube boilers and associated burner controls
Common in Mid-South
Burnham Commercial
Series 4, 5, V8H, Series 2 and cast iron sectional boilers
Common in Mid-South
Weil-McLain
Gold, Gold Plus, EG, PEG, 88 series and associated controls
Schools & Commercial
Bryan Steam
Flexible watertube (FLX) and bent water tube (PWT) industrial steam and hot water boilers
Industrial
Parker Boiler
Vertical tubeless steam and water heating boilers
Food & Process
Fulton
Vertical fire-tube steam and hot water boilers
Food & Process

Common Commercial Boiler Problems

These are the most common commercial boiler service calls we support across the Mid-South — what's causing them and where to start.

Boiler Troubleshooting — Common Field Issues

Reference guide for facility managers and boiler operators. Always have a qualified boiler technician perform safety-critical repairs.

Burner locks out on ignition — won't light
Check gas supply pressure and shutoff valve. Verify pilot is igniting (listen/feel for click on gas valve). Check spark igniter — should hear continuous sparking during trial. Check flame rod position and condition. Flame signal below 1.25 Vdc on KDM display = amplifier or scanner issue. Check RM7800 KDM fault code for specific diagnosis.
Parts we stock: RM7800 relay modules, flame amplifiers, igniters → same-day shipping
Low water cutoff tripping — boiler shuts down
First: verify actual water level in gauge glass. If water level looks normal — float may be stuck or chamber may be fouled with sediment. Blow down the control and observe if float drops. If LWCO doesn't trip during blowdown, that is a safety failure — shut boiler down immediately. Check equalizing lines for blockage. On 150S/157S: nuisance trips at low pressure = upgrade to MD model.
Parts we stock: M&M 67, 150S, 157S, PS-800 → same-day shipping
Boiler leaking — water weeping from handhole
Handhole or manhole gasket failure. If the gasket has been in service more than one season, replacement is the right call — do not attempt to re-torque your way out of a failed gasket. Identify the boiler operating pressure and specify the correct Topog-E® series: Series 180 for under 180 psi steam, Series 450 for up to 450 psi. Using the wrong series for your pressure is a safety issue.
We stock Topog-E® Series 180, 450 → same-day shipping. Call with your boiler model for gasket size.
Boiler cycling rapidly — short cycling on pressure
Differential on pressuretrol is too narrow — boiler reaches pressure setpoint quickly and shuts down, then restarts within minutes. Widen the differential on the pressuretrol or operating control. Also check for oversized boiler relative to building load (common in older installations), or excessive piping heat loss. On modulating systems, check setpoint programming and modulation range.
Check our resource guides: RM7800 Burner Control Guide covers modulating control setup in detail.
Steam boiler priming / surging water line
Water is carrying over into steam piping — caused by high dissolved solids (TDS) in boiler water, excessive boiler firing rate, or improper water treatment. Check boiler water conductivity — should typically be under 3,500 µS/cm for low pressure steam. If TDS is high, increase surface blowdown frequency. Check near-boiler piping — undersized header or Hartford Loop issues can cause surging that looks like priming.
Surging water line can cause nuisance LWCO trips — probe-type PS-800 with DOB/DOM delay may help.
Annual inspection failed — items to address
Most common inspection failures: LWCO not tripping during blowdown test (replace control), handhole/manhole gaskets showing leakage or age (replace with correct Topog-E® series), burner control not cycling correctly (service or replace relay module), safety valve lifting below set pressure or failing to reseat (replace safety valve — never adjust or wire down a safety valve). Address all items before returning boiler to service.
We can supply all parts needed to clear inspection items — call with your failure list.

Commercial Boiler Service Across the Mid-South

We support commercial boiler and HVAC service throughout the following areas. Don't see your city? Call us — our reach extends throughout the five-state region.

Memphis
Tennessee
Nashville
Tennessee
Knoxville
Tennessee
Chattanooga
Tennessee
Jackson
Tennessee
Little Rock
Arkansas
Fort Smith
Arkansas
Jonesboro
Arkansas
Pine Bluff
Arkansas
El Dorado
Arkansas
Jackson
Mississippi
Tupelo
Mississippi
Gulfport
Mississippi
Hattiesburg
Mississippi
Meridian
Mississippi
Birmingham
Alabama
Huntsville
Alabama
Mobile
Alabama
Montgomery
Alabama
Tuscaloosa
Alabama
New Orleans
Louisiana
Baton Rouge
Louisiana
Shreveport
Louisiana
Lake Charles
Louisiana
Lafayette
Louisiana

Know Your Equipment Before Service Day

Our in-depth technical guides cover the most common commercial boiler controls in the Mid-South. Use them to diagnose problems, spec replacements, and prepare for service visits.

Ready to Get Your Boiler Taken Care Of?

Tell us your boiler type, what's happening, and where you're located. We'll respond fast and get you moving in the right direction.

Frequently Asked Questions

What types of commercial boilers do you service?
We support service on all major commercial boiler types — fire-tube (Scotch marine), water-tube, cast iron sectional, condensing, electric, and steam generators. This covers both steam and hot water systems, gas and oil fuel, from low-pressure residential cast iron to high-pressure industrial water-tube boilers. Manufacturers we commonly service include Cleaver-Brooks, Burnham, Weil-McLain, Bryan Steam, Parker, and Fulton, among others. If your boiler manufacturer isn't listed, call us — we've likely seen it.
Do you cover boiler service in Arkansas, Mississippi, Alabama, and Louisiana?
Yes — our service coverage spans Tennessee, Arkansas, Mississippi, Alabama, and Louisiana. We're based in Memphis and have been serving the Mid-South since 1967, so we have established relationships and deep familiarity with the commercial and industrial boiler infrastructure throughout the region. Call us with your location and we'll get you connected with the right resources.
How often should a commercial steam boiler be inspected?
State boiler codes in Tennessee, Arkansas, Mississippi, Alabama, and Louisiana require annual inspection by a licensed boiler inspector for most commercial boilers. Beyond the code-required inspection, best practice includes pre-season startup inspections, daily blowdowns on low water cutoff controls (per McDonnell & Miller's official maintenance guidelines for commercial applications), annual burner combustion analysis and tuning, and annual internal cleaning of the fireside and waterside surfaces. Burner controls should be functionally tested and flame signal verified at each annual inspection.
What causes a commercial boiler to fail annual inspection?
The most common annual inspection failures we see across the Mid-South: (1) Low water cutoff not tripping during blowdown test — the LWCO must shut down the burner when the water level drops during blowdown; if it doesn't, it's a safety failure requiring immediate replacement. (2) Handhole or manhole gaskets leaking or showing age deterioration — replace with the correct Topog-E® series for your operating pressure. (3) Safety valve lifting below set pressure or failing to reseat — never attempt to adjust a safety valve; replace it. (4) Burner control faults or improper flame signal. We stock the parts to address all of these and can ship same day on most items.
Can you help with boiler parts if our boiler is down right now?
Yes — that's exactly what we're here for. Memphis Control Center stocks common boiler controls including McDonnell & Miller low water cutoffs (Series 67, 150S, 157S, PS-800), Honeywell RM7800 series burner controls and flame amplifiers, Topog-E® boiler gaskets (Series 180 and 450 in most common sizes), and Bell & Gossett pumps and parts. Orders placed by 2 PM CT ship same day from Memphis. Call us at (901) 458-2000 with your boiler model and the part you need — we'll get it moving.
What is the difference between a burner control lockout and a low water cutoff shutdown?
A burner control lockout (the relay module requires manual reset) is triggered by the flame safeguard system — typically from a failure to establish flame during the trial for ignition, a loss of flame signal during run, or an internal control fault. The Power LED on the RM7800 will blink a fault code, and the KDM will display a specific fault message. A low water cutoff shutdown cuts power to the burner when the water level drops to the cutoff point — on float-type controls this is a safety switch opening, on probe-type controls the conductivity circuit breaks. Both can look similar from the outside (boiler not running) but have completely different root causes and different fixes. Our RM7800 burner control guide and McDonnell & Miller LWCO guide cover both in detail.
Do you handle preventive maintenance contracts for commercial boilers?
Contact us to discuss your facility's needs. We can help coordinate annual inspection prep, recommend preventive maintenance schedules based on the official manufacturer guidelines for your specific controls, and ensure you have the right replacement parts on hand before your next outage window. Call (901) 458-2000 or fill out our contact form.