Description
Fireye YP300 Programmer Module
BurnerLogix Series – Recycle Type with 4-Second Flame Failure Response Time
Overview
The Fireye YP300 is a plug-in programmer module designed for use with the Fireye BurnerLogix System. This module delivers precise and reliable burner sequencing with a recycle-type operation, low fire start, early spark termination, and a 4-second Flame Failure Response Time (FFRT).
It’s ideal for use on automatically ignited oil, gas, or combination fuel burners, and works seamlessly with the YB110 or YB230 chassis, appropriate flame amplifiers, and flame detectors.
Key Features
-
Recycle operation for systems requiring automatic burner restart after shutdown
-
Low fire start and early spark termination ensure efficient and safe light-off
-
4-second FFRT offers rapid flame detection for increased safety
-
Full compatibility with BurnerLogix smart displays (VFD or LCD)
-
Smart LED status indicators and lockout diagnostics
-
Modbus RS485 communication for integration and monitoring
-
Keypad-selectable parameters (with compatible display)
-
Remote reset and run/check functions
-
Revert-to-pilot feature allows increased burner turndown
Applications
-
Commercial and industrial burners
-
Boilers, ovens, dryers
-
Fuel/air ratio systems requiring advanced sequencing and flame monitoring
-
Facilities seeking centralized burner diagnostics and control
System Compatibility
The YP300 is compatible with the following Fireye components:
-
Chassis: YB110/YB230
-
Displays: ED510 (LCD) or ED500 (VFD) – local or remote mounting
-
Wiring Bases: Pre-wired or terminal block type
-
Flame Scanners: UV, self-check UV, flame rod, auto-check IR, integrated scanners
Technical Specs
Specification | Details |
---|---|
Product Type | Programmer Module |
Module Type | Recycle |
Flame Failure Response | 4 Seconds |
Keypad Selectable | Yes (with optional display) |
Spark Termination | Early spark termination |
Startup | Low fire start |
Communications | Modbus RS485 |
Display Support | LCD or VFD, remote or local mountable |
Operating Status View | Via LED or optional alpha-numeric display |