Description
RM7897C1000 On-Off Primary Control
Integrated Burner Control with Programmable Post Purge and Delayed Main Valve, 120 Vac
The RM7897C1000 is a microprocessor-based On-Off primary burner control for use in gas, oil, or combination fuel single burner applications. Designed for high-reliability safety sequencing, it includes programmable post purge, delayed main valve, and blinking LED fault annunciation. Post purge parameters are configurable using the optional S7800A1142 Keyboard Display Module.
Key Features
-
Automatic burner sequencing and flame supervision
-
Programmable post purge (via optional S7800A1142 display)
-
Blinking LED displays fault codes during safety shutdown
-
Interchangeable plug-in flame amplifiers
-
Selectable recycle or lockout on airflow or flame loss
-
Supports delayed main valve operation
-
Local and remote annunciation options
-
Retains system history with nonvolatile memory
-
Shutter drive output and airflow switch check
-
Compatible with expanded annunciators and system diagnostics software
-
Optional PC interface and report generation
-
Vibration tested: 0.5 G environment
Technical Specifications
Specification | Value |
---|---|
Application | On-Off Primary Control |
Voltage | 120 Vac |
Flame Establishing Period | 4 or 10 seconds (pilot) |
Interlocks | Selectable |
Prepurge | Determined by ST7800A Purge Timer Card |
Postpurge | Programmable via S7800A1142 |
Delayed Main Valve | Yes |
Pilot Type | Selectable |
Vibration Rating | 0.5 G |
Memory | Nonvolatile |
Reset Options | Local or optional remote |
LED Indicators | 5 sequence LEDs, blinking fault code |
Mounting | On Q7800A/B Subbase (required) |
Required Components
-
Subbase: Q7800A or Q7800B Universal Wiring Subbase
-
Amplifier: R7847, R7848, R7849, R7851, R7852, R7861, or R7886
-
Purge Timer: ST7800A Plug-in Purge Timer Card
-
Display (optional): S7800A1142 for post purge setup
Common Applications
-
Commercial and industrial burner systems
-
Boilers, process heating systems
-
Safety-focused On-Off ignition systems requiring post purge and main valve delay