Description
V8944B1027 Diaphragm Gas Valve
Two-Stage Pressure Regulating, Slow Opening, 1-1/4" NPT, Natural Gas, 24 Vac, 1600 CFH
The V8944B1027 is a two-stage, slow-opening diaphragm gas valve designed for use in commercial heating applications requiring precise dual-stage control. It is part of the V4944/V8944B,C,L,N series — a reliable line of solenoid-operated gas valves that combine pressure regulation and safety shutoff in one rugged assembly.
Key Features
-
Two-stage operation offers smooth light-off and optimized flame control
-
Slow-opening design (3–25 sec) for gradual pressure ramp-up
-
Factory-preset regulator settings: 3.5" W.C. high fire, 0.8" W.C. low fire
-
Direct replacement for Honeywell V4844/V8844 series valves
-
Suitable for natural gas applications
-
Failsafe shutoff: valve closes on power loss
-
Die-cast aluminum construction with straight-through flow design
-
Includes 1/8" pilot tapping and dual bleed tappings (5/16" UNF)
-
Pre-wired with three 30" leadwires and 1/4" spade terminals
-
Designed for horizontal upright mounting
Technical Specifications
Specification | Value |
---|---|
Valve Type | Two Stage, Slow Opening |
Pipe Size | 1-1/4" NPT |
Voltage | 24 Vac |
Fuel Type | Natural Gas |
Inlet Pressure (Max) | 1/2 psi |
Capacity | 480 – 1600 CFH |
High Fire Setpoint | 3" – 4.5" W.C. (Factory: 3.5") |
Low Fire Setpoint | 0.8" – 2" W.C. (Factory: 0.8") |
Valve Opening Time | 3 – 25 seconds |
Valve Closing Time | ≤ 2 seconds |
Pilot Tapping | 1/8" NPT |
Bleed Tappings | (2) 5/16"-24 UNF |
Body Material | Aluminum |
Mounting Orientation | Horizontal, Upright |
Operating Temp Range | -40°F to 150°F |
Termination | 1/4" Spade Terminals, (3) 30" Leads |
Series Information
-
Natural Gas Models: V4944B, V8944B, V4944N, V8944N
-
LP Gas Models: V4944C, V8944C, V4944L, V8944L
-
Used with: Dual-stage 24 Vac thermostats or controllers (V8944), or line-voltage dual-stage controllers (V4944)
-
Direct replacement for V4844 and V8844 valve models
Common Applications
-
Commercial boilers and unit heaters
-
Duct furnaces and rooftop heating units
-
Make-up air systems
-
Systems needing staged gas flow with reliable safety shutoff