Description
V4943A1029 On/Off Diaphragm Gas Valve, 120Vac, 1-1/4", 1600 CFH Capacity, Straight Through, Non-Offset, 1/8"-27 NPT Pilot Tapping, 1/2 PSI Pressure Rating
Overview:
V4943A/V8943A are on/off diaphragm gas valves designed for boilers, unit heaters, duct furnaces, makeup air, and rooftop heaters.
Features:
-
Replacement for V4843A/V8843A gas valves
-
Suitable for atmospheric boilers, commercial water heaters, and rooftop heaters
-
Solenoid-operated diaphragm valves for on/off flow control of natural or LP gas
-
Die-cast aluminum valve body with straight-through flow pattern
-
V4943 models operate on line voltage on/off controllers; V8943A models operate with 24 Vac thermostats or controllers
-
Valve closes on power failure; recommended for final shutoff service
-
Rapid opening with internal bleed
-
Maximum valve opening time: 6 seconds
-
Maximum valve closing time: 3 seconds
-
Two 30" leadwires included
Specifications:
Specification | Value |
---|---|
Capacity (CFH) | 1600 |
Pressure Rating | 1/2 psi |
Size | 1-1/4" |
Voltage | 120v AC |
Fuel Type | Natural Gas, Propane |
Temperature Range | -40°F to 150°F |
Minimum Temperature | -40°F |
Maximum Temperature | 150°F |
Mounting | Horizontal |
Material | Aluminum |
Valve Type | On-Off, Rapid Opening |
Applications:
-
Atmospheric boilers
-
Commercial water heaters
-
Rooftop heaters
-
Unit heaters
-
Duct furnaces
-