Honeywell RM7897A2002 On-Off Primary Burner Control with Programmable Post Purge, Shutter Drive Output, and LED Fault Annunciation – 120V

Honeywell

SKU:
RM7897A2002
$886.41
$886.41

Description

RM7897A2002 On-Off Primary Control
Integrated Burner Control with Shutter Drive Output and Programmable Post Purge, 120 Vac

The RM7897A2002 is a microprocessor-based On-Off primary burner control designed for gas, oil, or combination fuel single burner applications. This control offers advanced sequencing and safety functionality, including programmable post purge, airflow switch checking, and shutter drive output. Post purge settings are configured using the optional S7800A1142 Keyboard Display Module.

Key Features

  • Integrated automatic burner sequencing and flame supervision

  • Programmable post purge via S7800A1142 display (not included)

  • Shutter drive output for additional combustion air control

  • Blinking LED fault annunciation with five-segment sequence display

  • Interchangeable plug-in flame amplifier support

  • Selectable recycle or lockout on airflow or flame loss

  • Local or remote system status and fault annunciation

  • Retains operating history and sequencing data in nonvolatile memory

  • Supports remote reset and optional PC interface

  • Compatible with expanded annunciator and COMBUSTION SYSTEM MANAGER™ software

Technical Specifications

Specification Value
Application On-Off Primary Control
Voltage 120 Vac
Flame Establishing Period 4 or 10 seconds (pilot)
Interlocks Selectable
Prepurge Determined by ST7800A Purge Timer Card
Postpurge Programmable via S7800A1142
Shutter Drive Output Yes
Delayed Main Valve No
Memory Nonvolatile
Reset Options Local or optional remote
LED Indicators 5 sequence LEDs, blinking fault code
Mounting On Q7800A/B Subbase (required)
Display Support S7800A1142 for post purge programming

Required Components

  • Subbase: Q7800A or Q7800B Universal Wiring Subbase

  • Amplifier: R7847, R7848, R7849, R7851, R7852, R7861, or R7886

  • Purge Timer: ST7800A Plug-in Purge Timer Card

  • Display (optional): S7800A1142 for post purge setup

Common Applications

  • Industrial and commercial boilers

  • Process heating systems

  • Burner systems requiring post purge and shutter control

Extra Information

Brand:
Honeywell
Weight:
2.50 LBS