Description
RM7896D1027 On-Off Primary Control
Pre & Post-Purge Burner Control with Interrupted Pilot and Dynamic Airflow Switch Testing, 120 Vac
The RM7896D1027 is a microprocessor-based integrated On-Off primary burner control designed for semi-automatic industrial gas, oil, coal, or combination fuel burners. It offers enhanced safety, sequencing, and diagnostics features, including pre- and post-purge, interrupted pilot operation, dynamic airflow switch testing, and delayed main valve control.
Key Features
-
Integrated automatic burner sequencing with interrupted pilot
-
Pre-purge and programmable post-purge sequences
-
Airflow switch check ensures safety interlock before ignition
-
Optional PC interface, keyboard display module, remote annunciation, and COMBUSTION SYSTEM MANAGER™ software
-
Five LEDs provide visual sequence status and fault indication
-
Supports interchangeable plug-in flame signal amplifiers
-
Nonvolatile memory retains data and fault history after power loss
-
Selectable relight or lockout on flame failure
-
Optional local or remote annunciation and reset capability
-
Optional report generation and system diagnostics
-
Delayed main valve operation for enhanced startup safety
Technical Specifications
Specification | Value |
---|---|
Application | On-Off Primary Control with Pre & Post Purge |
Voltage | 120 Vac |
Pilot Type | Interrupted |
Interlocks | Selectable |
Prepurge | Determined by ST7800A Purge Timer Card |
Postpurge | Yes (configurable) |
Airflow Switch Test | Dynamic AFS check included |
Memory | Nonvolatile |
Reset Options | Optional Remote or Local |
LED Indicators | 5 sequence status LEDs |
Delayed Main Valve | Yes |
Required Components
-
Subbase: Q7800A or Q7800B Universal Wiring Subbase
-
Amplifier: R7847, R7848, R7849, R7851, R7852, R7861, or R7886
-
Purge Timer: ST7800A Plug-in Purge Timer Card
Common Applications
-
Semi-automatic industrial burners (gas, oil, coal, or combination)
-
Systems requiring strict safety shutdown and sequencing logic
-
Equipment demanding airflow verification and delayed main valve