Description
RM7896C1010 On-Off Primary Control
Pre & Post-Purge Burner Control with Interrupted Pilot, 120 Vac
The RM7896C1010 is a microprocessor-based On-Off primary burner control designed for industrial and commercial gas, oil, or combination fuel single-burner applications. It provides enhanced safety features including pre-purge and post-purge, interrupted pilot operation, and plug-in amplifier compatibility.
Key Features
-
Integrated burner sequencing, flame supervision, and diagnostics
-
Interrupted pilot operation
-
Programmable pre- and post-purge sequences (post-purge programmable with S7800A1142)
-
Interchangeable plug-in flame amplifiers for flexible sensing
-
Blinking LED fault annunciation with 5 sequence status indicators
-
Supports optional keyboard display, PC interface, remote annunciation, and COMBUSTION SYSTEM MANAGER™ software
-
Retains system status and fault history in nonvolatile memory after power loss
-
Optional local or remote reset and report generation
-
Selectable relight or lockout on flame loss
-
Includes airflow switch check and delayed main valve
Technical Specifications
Specification | Value |
---|---|
Application | On-Off Primary Control with Pre & Post Purge |
Voltage | 120 Vac |
Pilot Type | Interrupted |
Interlocks | Selectable |
Prepurge | Determined by ST7800A Purge Timer Card |
Postpurge | Programmable with S7800A1142 Display |
Flame Establishing Time | 4 or 10 seconds |
Airflow Switch Check | Yes |
LED Indicators | 5 status/fault LEDs |
Delayed Main Valve | Yes |
Memory | Nonvolatile |
Reset Options | Local or Remote |
Required Components
-
Subbase: Q7800A or Q7800B Universal Wiring Subbase
-
Amplifier: R7847, R7848, R7849, R7851, R7852, R7861, or R7886
-
Purge Timer: ST7800A Plug-in Purge Timer Card
Common Applications
-
Industrial and commercial single-burner systems
-
Applications requiring interrupted pilot and post-purge control
-
Systems needing full safety sequencing and diagnostics