Honeywell RM7895C1012 Burner Control Relay Module, Interrupted/Intermittent Pilot, 120V

Honeywell

SKU:
RM7895C1012
$1,119.20
$1,119.20

Description

RM7895C1012 On-Off Primary Control
Prepurge, Interrupted Pilot, 120 Vac, Shutter Drive Output, Valve Proving, Blinking LED Fault Annunciation

The RM7895C1012 is a microprocessor-based On-Off primary burner control designed for automatically or semi-automatically fired single burner systems using gas, oil, coal, or combination fuels. It supports prepurge, shutter drive output, and includes a valve proving feature, delivering advanced burner sequencing and safety diagnostics in demanding industrial applications.

Key Features

  • Integrated prepurge function ensures combustion chamber safety prior to ignition

  • Interrupted pilot with flame establishing time of 4 or 10 seconds

  • Main burner flame establishing period: 10 seconds

  • Delayed main valve feature for improved burner sequencing

  • Valve proving support when used with S7800A1142 display (not included)

  • Shutter drive output compatible with mechanical air dampers

  • Automatic burner sequencing and flame supervision

  • Diagnostic LEDs provide live system status and fault codes

  • Interchangeable plug-in flame amplifiers allow flexible flame detection

  • Nonvolatile memory retains lockout and operational data after power loss

  • Optional keyboard display, PC interface, remote annunciation, and reset

  • Selectable relight or lockout on flame loss

  • Supports airflow switch check to ensure proper combustion airflow

Technical Specifications

Specification Value
Application On-Off Primary Control with Prepurge
Voltage 120 Vac
Pilot Type Interrupted
Prepurge Determined by ST7800A Purge Timer Card
Main Flame Establishing Time 10 seconds
Pilot Flame Establishing Time 4 or 10 seconds
Delayed Main Valve Yes
Valve Proving Yes (with S7800A1142)
Shutter Drive Output Yes
Interlocks Selectable
LED Indicators 5 status/fault LEDs
Memory Nonvolatile
Reset Options Optional Remote or Local

Required Components

  • Wiring Subbase: Q7800A or Q7800B

  • Flame Amplifier: R7847, R7848, R7849, R7851, R7852, R7861, or R7886

  • Purge Timer: ST7800A Plug-in Purge Timer Card

Common Applications

  • Semi-automatic industrial burners using gas, oil, or coal

  • Systems requiring prepurge and delayed main valve operation

  • Burner systems with airflow verification and shutter damper control

  • Applications needing enhanced diagnostic capabilities and valve proving

Extra Information