Description
Honeywell C6097B3028 Pressure Switch – Manual Reset, 1/4" NPT, 1 to 20 in. W.C., Subtractive
The Honeywell C6097B3028 is a robust manual-reset pressure switch designed for safety in positive, negative (air/flue gas), or differential pressure systems. It features a diaphragm-actuated mechanism to detect pressure rises, breaking the control circuit to prevent unsafe conditions. Built for durability and safety, it includes a transparent cover, external manual reset button, and is rated IP65 for protection in demanding environments.
Key Features
-
Manual reset pressure switch with external reset button for safety lockout
-
Diaphragm-actuated safety-limit switch for reliable pressure sensing
-
Breaks normally closed (NC) to common (COM) circuit on pressure rise (subtractive)
-
Suitable for gas and air pressure monitoring in HVAC and combustion systems
-
Transparent removable cover protects scaleplate and adjustment knob
-
Additional inlet filter pad for gas/air protection
-
Safety cover over screw terminals
-
Optional switch position indicator lamp available
-
IP65 rated enclosure for dust and water resistance
-
Certified by FM and UL for safety compliance
Technical Specifications
Parameter | Details |
---|---|
Product Type | Manual Reset Pressure Switch |
Pressure Range | 1 to 20 in. W.C. (water column) |
Switch Operation | Manual reset |
Switch Action | Breaks NC to COM on pressure rise (subtractive) |
Application | Positive/negative pressure or differential pressure sensing (gas, air, flue gas) |
Mounting | 1/4 in. Rp internal thread |
Pipe Connection | Vent or low pressure – 1/8 in. Rp internal thread |
Electrical Connections | Screw terminals; M16 x 1.5 cable gland |
Operating Temperature | -4°F to 176°F (-20°C to 80°C) |
Enclosure Protection | IP65 |
Dimensions (in.) | 3.19 H x 3 W x 3.7 D |
Certifications | FM (Class 3510), UL |
Additional Features | External manual reset button, transparent cover, filter pad, optional indicator lamp |
Ideal Applications
-
HVAC safety and pressure control
-
Combustion air and flue gas pressure monitoring
-
Positive and negative pressure sensing in gas or air systems